Whether you want your commercial boilers and water heaters powered by a mechanical draft system on the exterior of the building or inside the boiler room, ENERVEX has you covered.
Our CASV Chimney Automation System delivers state-of-the-art, multi-application exhaust for termination installations. It is a demand-controlled exhaust system designed for commercial boilers and heaters which optimizes any heating appliance’s efficiency by actively controlling draft. Its high temperature variable-speed draft fan and motor controls regulate draft by modulating the fan.
The CASV system consists of a single (or multiple) RSV, Chimney Fan and the EBC31, Modulating Fan Control. The EBC31 maintains a constant draft for the heating appliances by modulating the speed of the chimney fan. An MSC EDrive Motor Speed Controller is also part of the system when Chimney Fans with 1HP or more are used.
Each appliance is interlocked with the EBC 31. A call for heat activates the chimney fan and releases the burner once an adequate, pre-set draft is established. The sequence is repeated every time a new heating appliance calls for heat. When an appliance shuts down, the chimney fan will slow down while still maintaining the draft setting. When the last appliance shuts down the chimney fan will operate in post-purge mode for a preset time period.
The integrated proven draft function will shut down the entire system in case of a power failure to the chimney fan or the MSC Motor Speed Controller or mechanical failure. During a following call for heat, the Operating Priority function will detect if one or more appliances can be operated safely and with proper draft. If so, the appliance(s) will be able to operate without fan operation. After two (2) hours, fan operation is checked and if present, the control will go back to normal operation. Otherwise, it will continue to operate in Operating Priority mode. The self-check is repeated every two (2) hours infinitely. During a period without fan operation, the control is in alarm mode.
If the chimney fan has been out of commission for seven (7) days, the Bearing Cycle Activation function will operate the fan at a low speed for a short time. This is automatically repeated every seven (7) days, if the fan has not been operating.
Any errors detected during operation are shown on the digital display screen.
High-temperature mechanical draft fan designed for termination mounting. For vertical or horizontal installation. Used with condensing or non-condensing heating appliances.
A sophisticated multi-use draft and pressure controller with integrated webserver and remote access used with fans and dampers to monitor and maintain a constant pressure in commercial boiler and building applications.
A full featured, industrial-type motor controller programmed specifically to control and adjust the speed of ENERVEX fans and ventilators using Electronically Commutated (EC) Motors or Induction Motors.